Tél: +86-13333857585 E-mail: enquête@otywell-tector.com

À propos Contact |

Détecteur de flamme infrarouge S600-Exir3-UV (Trois UV IRS UV, Type de feuille de flambeau) - Otywell | Fabricant d'analyseurs de gaz

Détecteur de flamme/

Détecteur de flamme infrarouge S600-Exir3-UV (Trois UV IRS UV, Type de feuille de flambeau)

Response spectral range4.4μm, 5.0μm, 3.8μm, 185-260nm

Response time6s

Viewing angle range≤110 °

Detection distanceClass I

Température ambiante:-10 ~ 55

Environmental humidity≤95% RH

Pressure range86 ~ 106Kpa

Working voltageDC24V

Working currentcurrent≤25mA, alarm current≤35mA

Executive standardGB15631-2008, GB12791-2006

Explosion-proof gradeEXdⅡCT6

Protection gradeIP66

Signal outputSwitching relay contact output, RS-485 (built-in DIP switch, can set the address of the detector)

Installation methodwall or ceiling

Cable outlet thread20mmX1.5mm free conversion G1 / 2 facultatif

Dimensions(190X160X110) mm

Shell materialdie-cast aluminum

Weight1Kg

Advantagesétanche à la poussière, explosion-proof, corrosion-proof

  • Détails du produit

Description

S600-ExIR3-UV point-type infrared flame detector contains three infrared sensors and optical filters. The main sensor has the highest sensitivity to the CO2 emission spectrum (4.4μm) produced by the combustion of hydrocarbons, and the other three infrared sensor pairs The detection of ambient light and background light interference from thermal body radiation. The detector has multiple signal processing algorithms, combined with the logical comprehensive judgment of the flame flicker frequency, to maximize the suppression of false alarms and the best fire detection performance. The special fire signal processing method and multi-sensor detection technology greatly improve the sensitivity and response time of the detector. The sensitivity of the detector can be adjusted automatically according to changes in the use environment. The detector is suitable for liquid and gas fires, open flames accompanied by smoke, and places where deflagration occurs.

Fonctions fonctionnalités

Paramètres techniques

Response spectral range 4.4μm, 5.0μm, 3.8μm, 185-260nm
Response time 6s
Viewing angle range ≤110 °
Detection distance Class I
Température ambiante -10 ~ 55
Environmental humidity ≤95% RH
Pressure range 86 ~ 106Kpa
Working voltage DC24V
Working current current≤25mA, alarm current≤35mA
Executive standard GB15631-2008, GB12791-2006
Explosion-proof grade EXdⅡCT6
Protection grade IP66
Signal output Switching relay contact output, RS-485 (built-in DIP switch, can set the address of the detector)
Installation method wall or ceiling
Cable outlet thread 20mmX1.5mm free conversion G1 / 2 facultatif
Dimensions (190X160X110) mm
Shell material: die-cast aluminum
Weight 1Kg
Advantages étanche à la poussière, explosion-proof, corrosion-proof

Crévuré:

Suivant: