Tel: +86-13333857585 Correo electrónico: consulty@otywell-detector.com

Acerca de Contacto |

Detector de llama infrarroja S600EX-IR3 (Triple IR, Explosión) - Otywell | Fabricante de analizador de gas

Detector de llamas/

Detector de llama infrarroja S600EX-IR3 (Triple IR, Explosión)

Response spectral range4.4μm, 5.0μm, 3.8μm

Tiempo de respuesta:6s

Viewing angle range≤110 °

Detection distanceClase I

Temperatura ambiente:-10 ~ 55 ℃

Environmental humidity≤95% RH

Pressure range86 ~ 106Kpa

Working voltageDc24v

Working currentcurrent≤25mA, alarm current≤35mA

Executive standardGB15631-2008

Explosion-proof gradeEx d ⅡC T6 Gb

Protection gradeIP66

Signal outputSwitching relay contact output, RS-485 (built-in DIP switch, can set the address of the detector)

Installation methodwall or ceiling

Cable outlet thread20mmX1.5mm free conversion G1 / 2 opcional

Dimensiones:(190X160X110) mm

Shell materialdie-cast aluminum

Peso:1Kg

Advantagesa prueba de polvo, explosión, corrosion-proof

  • Detalles del producto

Descripción

The S600-ExIR3 three-wavelength point-type infrared flame detector contains three infrared sensors and optical filters. The main sensor has the highest sensitivity to the CO2 emission spectrum (4.4 μm) generated by the combustion of hydrocarbons, and the other two infrared sensor pairs The detection of ambient light and background light interference from thermal body radiation. El detector tiene múltiples algoritmos de procesamiento de señales, combined with logical comprehensive judgment of the flame flicker frequency, to maximize the suppression of false alarms and the best fire detection performance. The special fire signal processing method and multi-sensor detection technology greatly improve the sensitivity and response time of the detector. El detector es adecuado para incendios líquidos y de gas, open flames with smoke and places where deflagration occurs.

Funciones de funciones

Parámetros técnicos

Response spectral range 4.4μm, 5.0μm, 3.8μm
Tiempo de respuesta 6s
Viewing angle range ≤110 °
Detection distance Clase I
Temperatura ambiente -10 ~ 55 ℃
Environmental humidity ≤95% RH
Pressure range 86 ~ 106Kpa
Working voltage Dc24v
Working current current≤25mA, alarm current≤35mA
Executive standard GB15631-2008
Explosion-proof grade Ex d ⅡC T6 Gb
Protection grade IP66
Signal output Switching relay contact output, RS-485 (built-in DIP switch, can set the address of the detector)
Installation method wall or ceiling
Cable outlet thread 20mmX1.5mm free conversion G1 / 2 opcional
Dimensiones (190X160X110) mm
Shell material: die-cast aluminum
Peso 1Kg
Advantages a prueba de polvo, explosión, corrosion-proof