説明
GDB12 gas alarm controller is a multi-point monitoring gas alarm developed by our company. It is used to detect the concentration of the gas to be tested in the ambient air. 被測定ガスの濃度があらかじめ設定した警報値以上になったとき, the controller immediately sends out an audible and visual alarm to remind us to take safety measures in time, and start the execution equipment to control the drive exhaust or other external control equipment to prevent poisoning accidents, explosions, and fires, thereby ensuring the safety of life and property. The controller adopts a modular point-to-point structure design, which is simple to operate on site and easy to replace, making it easy for users to use and maintain.
技術的なパラメーター
★取り付け方法: 壁掛け式
★Use environment: indoor use
★Working voltage: AC220V
★Rated power: 2W/channel
★Working current: 0.01A/channel
★Full load working current: (connected to detector) 0.03A/channel
★Backup power specification: 24VDC, 1.3Ah (non-standard)
★Display mode: four-channel digital direct display, 音と光のアラーム
★Alarm segment: high and low limit alarm, fault alarm
★アラームモード: sound alarm, LED light indication
★Communication method: standard RS485 output
★Relay output: two passive switch quantities; – – one DC24V pulse control contact; one AC220V pulse control;
★Relay output: contact capacity 3A, 250VAC
★Working environment temperature: -10°C~ 55°C
★Working environment humidity: 10~95% RH (non-condensing)
★Working environment pressure: 86~106Kpa
★Storage conditions: -20°C~70°C, 10~95 %RH (non-condensing)
★ Cable requirements:: three-wire 3*1.5mm2
★ Size: 295*226*85(mm)
★ Other accessories: Standard mounting plate and medium 8 anchor bolts