Tel: +86-13333857585 E-mail: indagry@otywell-detector.com

Di Contatto |

Rilevatore di fiamma a infrarossi S600-Exir2 (Doppia lunghezza d'onda, Tipo di fiamma) - Otywell | Produttore di analizzatore di gas

Rilevatore di fiamma/

Rilevatore di fiamma a infrarossi S600-Exir2 (Doppia lunghezza d'onda, Tipo di fiamma)

Response spectral range:4.4μm, 3.8μm

Tempo di risposta:6S

Viewing angle range≤110 °

Detection distanceClass I

Temperatura ambiente:-10 ~ 55 ℃

Environmental humidity≤95% RH

Pressure range:86 ~ 106Kpa

Tensione di lavoro:DC24V

Working currentcurrent≤25mA, alarm current≤35mA

Executive standardGB15631-2008

Explosion-proof gradeEX d ⅡC T6 Gb

Protection gradeIP66

Signal outputSwitching relay contact output, RS-485 (built-in DIP switch, can set the address of the detector)

Installation methodwall or ceiling

Cable outlet thread:20mmX1.5mm free conversion G1 / 2 opzionale

Dimensioni:(190X160X110) mm

Shell materialdie-cast aluminum

Peso:1Kg

Advantages:polvere, a prova di esplosione, corrosion-proof

  • Dettagli del prodotto

Descrizione

The S600-ExIR2 point infrared flame detector contains two infrared detection wavelength sensors and optical filters. The detector has high sensitivity to the CO2 emission spectrum (4.4 μm) generated by the combustion of hydrocarbons. Another infrared sensor Spectral detection of the interference of ambient light and hot body radiation. The detector performs complex logical operations on the detection results of the two parameters, combined with the comprehensive judgment of the flame flicker frequency in the event of a fire, can enable the product to suppress various environmental light interference False alarms caused. The detector is suitable for liquid and gas fires, open flames that produce smoke, and places where deflagration occurs.

Funzioni Caratteristiche

 

Parametri tecnici

Response spectral range 4.4μm, 3.8μm
Tempo di risposta 6S
Viewing angle range ≤110 °
Detection distance Class I
Temperatura ambiente -10 ~ 55 ℃
Environmental humidity ≤95% RH
Pressure range 86 ~ 106Kpa
Tensione di lavoro DC24V
Working current current≤25mA, alarm current≤35mA
Executive standard GB15631-2008
Explosion-proof grade EX d ⅡC T6 Gb
Protection grade IP66
Signal output Switching relay contact output, RS-485 (built-in DIP switch, can set the address of the detector)
Installation method wall or ceiling
Cable outlet thread 20mmX1.5mm free conversion G1 / 2 opzionale
Dimensioni (190X160X110) mm
Shell material: die-cast aluminum
Peso 1Kg
Advantages polvere, a prova di esplosione, corrosion-proof

 