Descripción
The S600-ExIR2 point infrared flame detector contains two infrared detection wavelength sensors and optical filters. The detector has high sensitivity to the CO2 emission spectrum (4.4 μm) generated by the combustion of hydrocarbons. Another infrared sensor Spectral detection of the interference of ambient light and hot body radiation. The detector performs complex logical operations on the detection results of the two parameters, combined with the comprehensive judgment of the flame flicker frequency in the event of a fire, can enable the product to suppress various environmental light interference False alarms caused. El detector es adecuado para incendios líquidos y de gas, open flames that produce smoke, and places where deflagration occurs.
Funciones de funciones
Parámetros técnicos
Response spectral range | 4.4μm, 3.8μm |
Tiempo de respuesta | 6s |
Viewing angle range | ≤110 ° |
Detection distance | Clase I |
Temperatura ambiente | -10 ~ 55 ℃ |
Environmental humidity | ≤95% RH |
Pressure range | 86 ~ 106Kpa |
Working voltage | Dc24v |
Working current | current≤25mA, alarm current≤35mA |
Executive standard | GB15631-2008 |
Explosion-proof grade | Ex d ⅱc t6 gb |
Protection grade | IP66 |
Signal output | Switching relay contact output, RS-485 (built-in DIP switch, can set the address of the detector) |
Installation method | wall or ceiling |
Cable outlet thread | 20mmX1.5mm free conversion G1 / 2 opcional |
Dimensiones | (190X160X110) mm |
Shell material: | die-cast aluminum |
Peso | 1Kg |
Advantages | a prueba de polvo, explosión, corrosion-proof |
Veloz