Response spectral range:4.4μm, 3.8μm

Tiempo de respuesta:6s

Viewing angle range≤110 °

Detection distance:Clase I

Temperatura ambiente:-10 ~ 55 ℃

Environmental humidity≤95% RH

Pressure range:86 ~ 106Kpa

Working voltage:Dc24v

Working currentcurrent≤25mA, alarm current≤35mA

Executive standard:GB15631-2008

Explosion-proof grade:Ex d ⅱc t6 gb

Protection grade:IP66

Signal outputSwitching relay contact output, RS-485 (built-in DIP switch, can set the address of the detector)

Installation methodwall or ceiling

Cable outlet thread:20mmX1.5mm free conversion G1 / 2 opcional

Dimensiones:(190X160X110) mm

Shell materialdie-cast aluminum

Peso:1Kg

Advantages:a prueba de polvo, explosión, corrosion-proof

  • Detalles del producto

Descripción

The S600-ExIR2 point infrared flame detector contains two infrared detection wavelength sensors and optical filters. The detector has high sensitivity to the CO2 emission spectrum (4.4 μm) generated by the combustion of hydrocarbons. Another infrared sensor Spectral detection of the interference of ambient light and hot body radiation. The detector performs complex logical operations on the detection results of the two parameters, combined with the comprehensive judgment of the flame flicker frequency in the event of a fire, can enable the product to suppress various environmental light interference False alarms caused. El detector es adecuado para incendios líquidos y de gas, open flames that produce smoke, and places where deflagration occurs.

Funciones de funciones

 

Parámetros técnicos

Response spectral range 4.4μm, 3.8μm
Tiempo de respuesta 6s
Viewing angle range ≤110 °
Detection distance Clase I
Temperatura ambiente -10 ~ 55 ℃
Environmental humidity ≤95% RH
Pressure range 86 ~ 106Kpa
Working voltage Dc24v
Working current current≤25mA, alarm current≤35mA
Executive standard GB15631-2008
Explosion-proof grade Ex d ⅱc t6 gb
Protection grade IP66
Signal output Switching relay contact output, RS-485 (built-in DIP switch, can set the address of the detector)
Installation method wall or ceiling
Cable outlet thread 20mmX1.5mm free conversion G1 / 2 opcional
Dimensiones (190X160X110) mm
Shell material: die-cast aluminum
Peso 1Kg
Advantages a prueba de polvo, explosión, corrosion-proof

 