Beschreibung
The S600-ExIR1 point infrared flame detector contains an infrared sensor and optical filter. The detector has the highest sensitivity to the CO2 emission spectrum (4.4 μm) generated by the combustion of hydrocarbons. Logic comprehensive judgment has high immunity to false alarms generated by environmental infrared light sources. Since the sunlight light source is relatively complex, and the detector uses only a single wavelength infrared sensor for flame detection, the product should be used in an indoor working environment. The detector is suitable for liquid and gas fires, open flames that produce smoke, and places where deflagration occurs.
Funktionen Funktionen






Technische Parameter
| Spectral range of response | 4.4μm |
| Ansprechzeit: | 6S |
| Betrachtungswinkelbereich | ≤110° |
| Erkennungsentfernung: | Klasse I |
| Umgebungstemperatur | -10 ~ 55 ℃ |
| Umgebungsfeuchtigkeit | ≤95 % relative Luftfeuchtigkeit |
| Druckbereich | 86 ~ 106 kPa |
| Arbeitsspannung | DC24V |
| Arbeitsstrom | monitoring current≤25mA, Alarmstrom ≤ 35 mA |
| Executive-Standard: | GB15631-2008 |
| Explosionsgeschützte Ausführung | Ex d ⅡC T6 Gb |
| Schutzgrad | IP66 |
| Signalausgang | Schaltrelais-Kontaktausgang, RS-485 (eingebauter DIP-Schalter, kann die Adresse des Melders einstellen) |
| Installationsmethode: | Wand oder Decke |
| Kabelausgangsgewinde | 20mmX1,5mm freie Konvertierung G1 / 2 optional |
| Abmessungen: | (190X160X110) mm |
| Schalenmaterial: | Aluminiumdruckguss |
| Gewicht | 1kg |
| Vorteile | Dustproof, explosionsgeschützt, korrosionsbeständig |
Otywell | Hersteller von Gasanalysator








Wechat
Scannen Sie den QR -Code mit WeChat